The Elite VF1480 analog addressable FACP with networked releasing, supports 2 or 4 SLC loops for a total of 500 primary points and up to 800 points using subpoints. SLC loop communications uses standardtwisted pair cabling, shielded cable is not necessary.
UL 864 9th Edition listed
Primary AC 120VAC @ 2 Amps 60hz (OPtional 240 VAC 50hz)
Output DC 24VDC @ 4 Amps
Power Supply 5.25 Amp regulated and intergrated
Charger Current 1.25 Amps Max
Display 8 line x 40 character LCD (320 characters total)
Zones 500 Zones per network
SLC Loops 2 or 4 (Class A or B)
Devices perloop 126 sensors & modules (800 addresses + sub-addresses max. per panel)
NAC Outputs (4) 1.6 Amp @ 24VDC (class B)
Relay Outputs (5) Form C 1 Amp @ 30VDC
Voltage Output (3) 500mA @ 24VDC, reverse polarity supervised
Aux Power 500mA @ 24VDC
Aux Inputs (3) digital pull downs